Installation and Programming Manual
40
1) System
The following parameters are used for programming configuration settings applicable to
the entire system (see page 33). With the display showing:
Quick Key Item Default Range Explanation
1 TIME DEFINE --- Specifies the Duration of an Action
1 1 Exit/Entry Delay 1 --- Entry/Exit Delays (Group 1)
1 1 1 1 Entry Delay 1 30 sec 0-255
duration of Group 1 Entry Delay
1 1 1 2 Exit Delay 1 45 sec 0-255
duration of Group 1 Exit Delay
1 1 2 Exit/Entry Delay 2 --- Entry/Exit Delays (Group 2)
1 1 2 1 Entry Delay 2 45 sec 0-255
duration of Group 2 Entry Delay
1 1 2 2 Exit Delay 2 60 sec 0-255
duration of Group 2 Exit Delay
1 1 3 Bell Timeout 04 min 01-90 duration of external sounder(s) during alarm
1 1 4 Bell Delay 00 min 00-90
The amount of delay before the external sounder
operates after the onset of an alarm; each keypad’s
sounder is unaffected by this value
1 1 5
Switched Auxiliary
Break
10 sec 01-90
Specifies the amount of time that the power supplied
to the system’s smoke detectors will be interrupted
during a user-initiated smoke detector reset, typically
performed after a Fire Alarm
1 1 6
Wireless Module
Times
--- time intervals relating to the operation of the wireless module
1 1 6 1 Jamming Time NONE
NONE
10 SEC
20 SEC
30 SEC
§ specifies the amount of time that the ORBIT-
Pro’s wireless module will tolerate unwanted
radio frequencies capable of blocking
(jamming) signals produced by the system’s
transmitters
§ once the specified time is reached, the panel
will send a Reporting Code to the Central
Station if so defined (see page 98)
§ if Audible Jamming=YES (see page 46), the
panel will also activate the external sounder
§ NONE means that the system will neither
detect nor produce any indication that signal
jamming has been detected
1 1 6 2
Supervisory (S.V.)
Time*
0 Hrs. 0-9
§ Specifies how often the ORBIT-Pro will check
for signals (e.g. supervisory, alarm, tamper, or
trouble) distinguishing each of the system’s
transmitters
§ The panel will generate a local trouble signal
identifying the zone of any transmitter from
which a signal was not received during the
specified interval
§ if so defined (see page 98) the panel will send
the Supervision Reporting Code to the Central
Station
§ “0 Hrs” disables supervision
*Not for UL Installations
INSTALL PROG:
1)SYSTEM
INSTALLER PROG:
1)SYSTEM
press [ENTER]. The first sub-category, TIME DEFINE, will
appear. You may access it by pressing [ENTER] OR by pressing
the [1] key.