Installation and Programming Manual
54
ZONES: TERMINATION
ZONES: LOOP RESPONSE
Quick Key Item Default Explanation
2 5
Zone
Termination
TERMINATION
--- § programs ONLY the terminations used for each of the
system’s zones
§ the actual (physical) termination for each zone must
be agree with that selected below
§ a listing and explanation of zone terminations can be
found in Figure 2-4 on page 22
§ to select the Zone Termination for any zone:
a) from this display, press [ENTER]
b) specify its two-digit Zone Number
c) press [ENTER] again, and select among the
following:
1 § uses normally-closed contact(s) and no terminating
End-of-Line Resistor (see page 22)
2
default for
all zones
§ uses normally-closed (NC) and/or normally-open (NO)
contacts in a zone terminated by a supplied 2200Ω
End-of-Line Resistor
3 § uses normally-closed (NC) contacts in a zone using at
least two 2200Ω End-of-Line Resistors to distinguish
between alarms and tamper conditions
2 5 xx
+
E
N
T
E
R
4 § uses normally-open contact(s) and no terminating
End-of-Line Resistor
2 6
Loop
Response
LOOP RESPONSE
--- § sets the minimum time for which a zone violation must
exist before the zone will trigger an alarm condition
§ to select the Zone Termination for any zone:
a) from this display, press [ENTER]
b) specify its two-digit Zone Number
c) press [ENTER] again, and select among the
following:
1 Normal
default for
all zones
500 ms (milliseconds)
2 Long 1 second
2 6
xx
+
E
N
T
E
R
3 Fast 10 ms (milliseconds)
INSTALLER PROG:
2)ZONES ↓↓
SUBJECT: ZONES
5)TERMINATION ××
6)LOOP RESPONS ××